Product Code : BGS-2
Brand Name : MRM PROCOM
Product Description

To deal with increasing market demand, we are engaged in offering Manual Controllers. Provided controllers are manufactured by our adroit engineers using pristine quality components and competitive techniques. Our quality engineers also check these controllers to deliver them defect free at the clients end. These controllers are mainly used for controlling as well as for monitoring various electrical parameters. As per the convenience of clients, we are providing these Manual Controllers at the most budgeted prices. 

Features:

  • Manually operated
  • Easy to operate
  • Reliable results
  • Rugged design

Manual Controllers

Protection, Supervision Salient features

  • Charging Alternator Fail/V-Belt
  • Oil Pressure
  • Run Hour (Optional). The charging alternator and LLOP Sensor should be connected to the system for this to work
  • HWT
  • RWL
  • Emergency
  • DG Over/Under Frequency
  • Low Fuel

Measurement & Display

  • BGS-2 equipped with LCD display and displays
  • Radiator Temp in degree centigrade
  • Generator Frequency
  • Fuel Level in %
  • Battery Voltage
  • Programmed settings
  • RPM
  • Run Hour (Optional)
  • Oil Pressure in KG/cm2

Normally the display auto scrolls and displays a set of parameter for 10 seconds, but any time the Next key (^) can be pressed to select the next parameter window.

Parameter Mode

Display

Explanation of parameter

Factory setting

Setting Range

Generator O/F

Over frequency setting

65 Hz

40 - 80 Hz

Gen O/F Delay

Monitoring time for Over frequency

5 Sec.

1-999Sec.

Generator U/F

Under frequency setting

45 Hz

40 - 80 Hz

Gen U/F Delay

Monitoring time for Under frequency

10 Sec.

1-999Sec.

Fuel Level in %

Level of fuel at which the Engine shall shut down

20% Sec.

10-100%

Fuel << delay

Monitoring time of Fuel Fault

5 Sec.

1-999Sec.

Low Lube Pressure

Level of LLOP at which the Engine shall shut down

2.0 Kg / Cm2

0-8.5 Kg / Cm2

LLOP delay

Monitoring time of LLOP Fault

5 sec.

1-999 sec.

High Water Temp.

Temperature of water at which the Engine shall shut down

80

0-150 Degree centigrade

HWT delay

Monitoring time of HWT Fault

5 Sec

1-999 Sec


Specifications

AC voltage withstand

330 VAC (Phase to neutral)

Measurement Accuracy


Voltage

1%

Surge 1.2/50 Usec

2.5KV

Battery Voltage

Suitable for 12V System

Min. voltage to power on

9V

Max. Battery Voltage

15V

DC Interruption time

0.5Sec.

Cut out Dimensions

92mm X 92mm

Depth

120mm

Digital Input Level

Battery Voltage (Negative) except Charging Alt, which is battery supply

It is our endeavour to constantly upgrade our products, hence specifications are subject to change without any notice.

Download PDF Fil


MRM PROCOM PVT. LTD.
X


Contact Details
  • MRM PROCOM PVT. LTD.
    Faridabad, Harayana, India
  • Plot No. 20-21, Sector 59, Phase-2, Faridabad - 121004, Haryana, India
  • Phone : +917042178359
  • Send Inquiry   Send SMS
  • Mr. Pankaj Gupta (Director)
  • Mobile : +917042178359
MRM PROCOM PVT. LTD. All Rights Reserved.(Terms of Use)
Developed and Managed by Infocom Network Ltd.